Regeltex
Model No.Class 00-04
Feature/ OverviewMax operating voltage (volts): 500 -36000
Proof test voltage (volts) 2500 - 40000
Withstand voltage (volts) 5000 - 50000
Back
full range of insulating gloves for live working complies with the specifications of the European standard EN 60903:2003 and the international standard IEC 60903:2002. Likewise, our production is subjected to a system for ensuring EC quality of production by means of monitoring to implement article 11b of the 89/686/EEC directive relating to Personal Protective Equipment which classifies insulating gloves for live working in category III (mortal risks). Summary table
*Obtaining the category authorises an additional thickness of O.6mm |
|
Class | Max operating voltage (volts) | Proof test voltage (volts) | Withstand voltage (volts) |
---|---|---|---|
00 | 500 | 2 500 | 5 000 |
0 | 1 000 | 5 000 | 10 000 |
1 | 7 500 | 10 000 | 20 000 |
2 | 17 000 | 20 000 | 30 000 |
3 | 26 500 | 30 000 | 40 000 |
4 | 36 000 | 40 000 | 50 000 |